If you are a HVAC/R technician, you should always check any air-source (ASHP) for proper airflow across the coils when troubleshooting or during preventive maintenance.

Correct airflow is of crucial importance to the operation of any ASHP. Part of the heat transfer rate is determined by the airflow across the indoor and outdoor coils. If the airflow is incorrect,
Crystal Bay MN 55323 then the heat transfer rate is incorrect and can drastically affect the equipment’s performance.
Accurate airflow measurement is essential in troubleshooting any system. In fact, no refrigeration test is valid if the air flow volume is not correct!

ASHP manufacturers follow the tenants of the Air Conditioning, Heating, and Refrigeration Institute (AHRI) which has a “Test Stand Value” requiring the Crystal Bay MN 55323 measured air volume rate, when divided by the measured indoor air-side total capacity, must not exceed 37.5 SCFM per 1,000 Btu/h [this is a maximum of 450 cubic feet per minute (CFM) of airflow across an indoor coil per 12,000 Btu/h of capacity]. Most manufacturers use an acceptable range of 350 to 450 CFM per 12,000 Btu/h of capacity, and
Crystal Bay MN 55323 over 750 CFM per 12,000 Btu/h of capacity across outdoor coils (most outdoor fans move approximately 1,000 CFM, up to 1,500 CFM, per 12,000 Btu/h of capacity). In the HVAC/R industry, 12,000 Btu/h of capacity is referred to as a “Ton” of refrigeration. Typically, most manufacturers focus on around 400 CFM per “Ton” when rating their equipment.

Before performing any airflow Crystal Bay MN 55323 determination, always make sure that all registers and grilles are open filters and coils are clean, and that blowers and fans are running properly delivering airflow across the indoor coil and the outdoor coil.
There are various methods that help determine the airflow amount across an indoor coil. The indoor coil is typically checked as the airflow must cross this coil Crystal Bay MN 55323 to allow the refrigerant to either absorb (ASHP cooling) or reject (ASHP heating) the heat to the appropriate “sink.” In summer, the “sink” is the outdoors, and during winter, the “sink” is indoors.

One of the most widely utilized methods when checking ASHP airflow has been the “temperature rise” method across the auxiliary or emergency (back up) heater(s). This method can Crystal Bay MN 55323 be performed regardless of outdoor ambient temperature.

When performing this test, you should remember that typically, most air source s operate with the same airflow regardless of mode of operation. In cooling or heating, or during emergency heat or defrost, the simply delivers the “same” airflow per ton across the indoor coil. The only change is possible during Crystal Bay MN 55323 the cooling mode, as water condensing on the indoor coil increases resistance slightly, lowering airflow amounts somewhat. Of course, you can also change blower speeds and CFM amounts for either cooling or heating on some ASHPs.

To check airflow (CFM) of an ASHP, you have to perform several measurements and use some math. The common formula for calculating CFM is:

Emergency Heat Crystal Bay MN 55323 Output(Btu/h)

CFM= —————————–

Temperature Rise x 1.08

You must find the CFM per Ton traveling through the indoor coil during cooling or heating modes. To accomplish this, you should place the system in the emergency heat mode and place thermometers in the supply air and return air paths as close to the air handler as possible without being affected by the radiant effect Crystal Bay MN 55323 of the heaters.

In the previous formula, CFM equals the emergency heat output in Btu/h. Since you will be checking heaters, you will be calculating electrical data. When finding Btu/h output of the heater, you will simply measure the voltage and the amperage at the disconnect for the heater(s) and record the values. This will require use of a voltmeter and Crystal Bay MN 55323 an ammeter.

Supply voltage multiplied by amperage equals wattage. Wattage multiplied by 3.413 (Btus per Watt) equals Btu/h and you will then have the value for the CFM formula numerator.

In the CFM formula denominator, temperature rise comes from the difference in the return air and supply air temperature after the heater(s) has/have stabilized and a difference has occurred. This difference (sometimes Crystal Bay MN 55323 called TR or �”T) is then multiplied by a constant of 1.08 to find the adjusted temperature difference. Always pay close attention to temperature change when finding the difference in temperature.

This adjusted temperature difference is the denominator for the CFM formula.
When the formula is completed with the necessary inputs, the answer is the total delivered airflow (CFM) traveling across the Crystal Bay MN 55323 heater in emergency heat mode. You then simply divide this value by the tonnage of the installed outdoor coil to find the CFM per ton. The cooling airflow (CFM) will be near to this value or slightly lower due to increased pressure drop from water condensing on the indoor coil during cooling. The ASHP compressor heating airflow (CFM) per ton Crystal Bay MN 55323 will be a similar value to that found from emergency heat. The CFM per ton should be in the AHRI range to be acceptable.

If inaccurate air flow (CFM volume) across the indoor coil (evaporator in cooling, condenser in heating) is determined, this situation must be corrected prior to further analysis of the refrigeration cycle.

Determining ASHP indoor coil airflow (CFM) during Crystal Bay MN 55323 emergency heat example:

Two (2) Ton Unit

240 Volts at disconnect

20 Amps at disconnect

Return air = 70ºF

Supply air = 88ºF
CFM = (240 x 20 x 3.413) ÷ (1.08 x 18ºF) = 843

843 CFM ÷ 2 Tons = 421.5 CFM per Ton

(This amount is acceptable per AHRI)

You should also check the outdoor coil for minimal clearance per manufacturer around the unit Crystal Bay MN 55323 from shrubs, trees, and decks to allow for proper heat rejection in the summer and absorption in the winter. You can also determine the airflow across the outdoor coil by using the product specifications from the manufacturer as shown below. Most ASHP outdoor coils will typically deliver close to this amount if the coil is installed correctly and unobstructed.

Phillip A. Crystal Bay MN 55323 Rains

air conditioning and refrigeration courses onlinehvac blower

Surrounding Areas In Minnesota

  • Heat Pump Training in Mapleton MN 56065
  • Heat Pump Training in Eveleth MN 55734
  • Heat Pump Training in Madison MN 56256
  • Heat Pump Training in Janesville MN 56048
  • Heat Pump Training in Brainerd MN 56401
  • Heat Pump Training in Cromwell MN 55726
  • Heat Pump Training in Waseca MN 56093
  • Heat Pump Training in Milan MN 56262
  • Heat Pump Training in Zumbrota MN 55992
  • Heat Pump Training in Lakefield MN 56150
  • Crystal Bay Information

    Video: Heat Pump in Crystal Bay MN

    [ssyelp location="Crystal Bay MN" term="schools" limit="10"]